Circular airflow measurement and commissioning damper. The CRM consists of a duct section with a damper and measuring device. The connections are fitted with rubber seal ring. The damper has a lockable knob for manual adjustment and indicators for open and closed damper blade position are stamped in the damper’s exterior surface.
Inside the damper, there is a measurement unit and a damper blade. The damper blade is available as a solid blade with rubber gasket (Ductwork leakage class 4), or as a perforated blade without rubber gasket (Ductwork leakage class 0). Ductwork leakage classification according to SS-EN1751 och VVS AMA 98. Tightness Classification according to EN 1751 and VVS AMA Pressure Class A with 1000 Pa as the highest pressure difference over damper blade in closed position. Tightness class C on the housing and tightness class 0 for closed damper.
When motorised control is selected, the damper knob shelf is replaced by a larger actuator support shelf. The motorised control requires an actuating torque. Standard supporting shelves are 80 mm high to allow possible duct insulation.