PELICAN Ceiling
- Flexible distribution pattern without change in the sound data
- Designed for modular suspended ceilings
- Commissioning box with 1 or 2 changes in dimension between the inlet and outlet
- Available in a version with low installation height
- ADAPTER for suspended ceiling system
- Standard colour White RAL 9003
- 5 alternative standard colours
- Other colours upon request
Technical description
The square, perforated supply air diffuser PELICAN Ceiling consists of a diffuser backing box and a diffuser face. The air diffuser's perforated face plate is equipped with an adjustable air flow director for simple variation of the distribution pattern. The diffuser face is easy to install and remove. This enables quick and uncomplicated installation, commissioning and cleaning.
The air diffuser is also available in a low version if the space inside the ceiling void is restricted. The air diffuser is then supplied without sleeve coupling (not size 400-600).
The diffuser backing box and the diffuser face are made of sheet steel. The commissioning box is made of galvanized sheet steel. The interior and exterior surfaces of the air diffuser are painted.
- Standard colour:
- White semi-gloss, lustre 40, RAL 9003/NCS S 0500-N
- Alternative standard colours:
- Silver gloss, lustre 80, RAL 9006
- Grey aluminium gloss, lustre 80, RAL 9007
- White semi-gloss, lustre 40, RAL 9010
- Black semi-gloss, lustre 35, RAL 9005
- Grey semi-gloss, lustre 30, RAL 7037
- Non-painted finish and other colours available on request.
SUPPLY AIR - AIR FLOW - SOUND PRESSURE ROOM (Lp10A) *) | |||||||
PELICAN Ceiling Supply Size | ALS Size | 25 dB(A) | 30 dB(A) | 35 dB(A) | |||
l/s | m3/h | l/s | m3/h | l/s | m3/h | ||
125-400/600 | 100-125 | 27 | 97 | 36 | 130 | 43 | 155 |
160-400/600 | 125-160 | 38 | 137 | 54 | 194 | 70 | 252 |
200-600 | 160-200 | 58 | 209 | 80 | 288 | 110 | 196 |
250-600 | 200-250 | 83 | 299 | 107 | 385 | 150 | 540 |
315-600 | 250-315 | 125 | 450 | 150 | 540 | 180 | 648 |
400-600 | 315-400 | 180 | 648 | 215 | 774 | 255 | 918 |
Data specified for supply air applies to 50 Pa total pressure. *) Lp10A = Sound pressure incl. A-filter with 4 dB room attenuation and 10 m2 room absorption area. | |||||||
EXTRACT AIR - AIR FLOW - SOUND PRESSURE ROOM (Lp10A) *) | |||||||
PELICAN Ceiling Extract Size | ALS Size | 25 dB(A) | 30 dB(A) | 35 dB(A) | |||
l/s | m3/h | l/s | m3/h | l/s | m3/h | ||
125-400 | 100-125 | 19 | 68 | 27 | 97 | 40 | 144 |
160-400 | 125-160 | 25 | 90 | 44 | 158 | 63 | 227 |
200-600 | 160-200 | 35* | 126* | 70 | 252 | 95 | 353 |
250-600 | 200-250 | 61 | 220 | 88 | 317 | 130 | 468 |
315-600 | 250-315 | 95 | 342 | 155 | 414 | 190 | 684 |
400-600 | 315-400 | 140* | 504* | 240 | 864 | 300 | 1080 |
Data specified for extract air applies to 50 Pa total pressure. *40 Pa total pressure. *) Lp10A = Sound pressure incl. A-filter with 4 dB room attenuation and 10 m2 room absorption area. |
Whilst we have made every effort to ensure information on this website is up to date and accurate, the technical specification and availability of products/services listed on this website may vary market to market and are subject to change without notice. Please contact your regional representative or visit your local website for further details.