ROE is an extract register in a reinforced design for ceiling or wall mounting. The terminal has been approved for use in prisons and can also be used in detention centres, care institutions, schools, etc.
You might want to visit our global site:
ROE is an extract register in a reinforced design for ceiling or wall mounting. The terminal has been approved for use in prisons and can also be used in detention centres, care institutions, schools, etc.
LUFTVOLUMENSTROM - SCHALLDRUCK RAUM (Lp10A) *) | |||||||
ROE Größe | 25 dB(A) | 30 dB(A) | 35 dB(A) | ||||
l/s | m3/h | l/s | m3/h | l/s | m3/h | ||
100 | 9 | 32 | 17 | 61 | 33 | 119 | |
125 | 18 | 65 | 33 | 119 | 45 | 162 | |
160 | 20 | 72 | 35 | 126 | 75 | 270 | |
200 | 24 | 86 | 38 | 137 | 79 | 284 | |
Daten gelten bei einem Gesamtdruckabfall von 100 Pa über dem Luftauslass. *) Lp10A = Schalldruck inkl. A-Filter mit 4 dB Raumdämpfung und 10 m2 Raumabsorptionsfläche. |
Dokument | Artikel | Dokumentart | Datum | Herunterladen |
---|---|---|---|---|
Montage, Einregulierung, Wartung (pdf 450.05kB) | ROEa | IOM-Handbuch | 17.07.2024 | |
Produktdarstellung - Luftauslass und Klappe (pdf 247.16kB) | Luftauslass und Klappe | Broschüre | 08.11.2021 | |
Abluftventil ROBUST (pdf 698.29kB) | ROEa | Technischer Katalog | 17.07.2024 | |
Einregulierungsleitfaden - Luftauslässe, VAV/CAV- & Einregulierungsklappen (pdf 7.68MB) | Luftauslässe, VAV/CAV- & Einregulierungsklappen | IOM-Handbuch | 19.08.2024 | |
Übersicht Luftauslässe (pdf 3.48MB) | Luftauslässe | Broschüre | 31.10.2023 |